ElmoMC SimplIQ Command Reference User Manual

Page 103

Advertising
background image

0x8000 0x4000 0x2000 Meaning

0 0 0 OK.
0

0

1

Under voltage. The power supply is shut down or it
has too high an output impedance.

0

1

0

Over voltage. The voltage of the power supply is too
high, or the servo drive did not succeed in absorbing
the kinetic energy while braking a load. A shunt
resistor may be required.

0 1 1 Reserved.
1 0 0 Reserved.
1

0

1

Short circuit. The motor or its wiring may be
defective, or the drive is faulty.

1

1

0

Temperature. Drive overheating. The environment is
too hot, or lacks heat removal. There may be a large
thermal resistance between the drive and its
mounting.

1 1 1 Reserved.

Table 3-31: Bits 13 - 15 of MF Report

Attributes:

Type:

Status report, Integer, Bit-field

Scope:

Program, RS-232, CANopen

Restrictions: None
Unit modes: All

Example:
The MF report of 0x3000 indicates that the motor has been shut down due to under
voltage. The under-voltage condition did not necessarily exist at the time the MF was
reported. It may possibly be the result of high power consumption and a high output
impedance of the power supply. In such a case, when the motor was shut down, the
power consumption stopped and the power supply returned to its normal voltage.

See also:

SR

,

MO

,

TS

,

LL[N]

,

HL[N]

,

CD

,

PE

,

VE

Reference chapter in the SimplIQ Software Manual:
Chapter 10, ”The Current Controller”

SimplIQ

Command Reference Manual

Alphabetical Listing

MAN-SIMCR (Ver. 4.5)

3-90