Xp[n] - extra parameters – ElmoMC SimplIQ Command Reference User Manual

Page 176

Advertising
background image

XP[N] - Extra Parameters

Purpose:
Includes system parameters, not commonly changed by the user, which enable the drive
to be adapted to special situations.

Index Value

Range Meaning

0

Reserved.

1

[BV/16 … BV]

XP[1] defines over/under voltage threshold.
Over voltage is activated at XP[1] volts.
Under voltage is activated at XP[1]/8 volts.

2 [0…4]

PWM

Fast

Medium Slow mode.

0 – Medium switching frequency, PWM switch once per
sampling time (TS)
1 – Slow switching frequency, PWM switches every two
sampling time.
2..4- Fast switching frequency, PWM switches XP[2] times
per sampling time

3

Reserved

4

[10…32,760]

Filter constant of bus voltage measurements.

5 [0…12,000] Limiter

for

input filter of current loop.

6

[0…2,147,483,647] Low-pass constant for input filter of current loop.

7 [0…8000] Maximum

counter

value

for Hall/encoder mismatch. If

value is 0, no Hall/encoder mismatch check occurs.

8, 9

Reserved.

Table 3-55: XP[N] Entries and Values

Notes:

ƒ

Changing XP[1] or XP[2] requires a retuning of the current controller parameters.

ƒ

For the Cello and Trumpet under-voltage is activated at 0.18*BV

ƒ

When XP[2] is higher than 1, excessive PWM switching frequency occurs. In this
case the drive’s maximum allowed current saturation (PL[1]) is reduced. The
amount of reduction depend upon the XP[2] value, the maximum bus voltage
threshold setting (XP[1]), the type of drive, and the maximum allowed current
(MC). To find out the actual maximum stall current threshold, use WS[34]. Use
WS[33] to find out the actual peak current saturation.

Attributes:

Type: Parameter,

Integer

Source:

Program, RS-232, CANopen

Restrictions: MO=0
Default values: XP[1]=BV,

XP[2]=0,

XP[4]=30720, XP[5]=1000

XP[6]=12000, XP[7]=0

Range: Previous

table

Unit modes: All
Activation: Immediate

SimplIQ

Command Reference Manual

Alphabetical Listing

MAN-SIMCR (Ver. 4.5)

3-163