8 configuring limit values, Configuring limit values, Er 4.8 – Rice Lake PR5220 Ethernet Transmitter User Manual

Page 102: Commissioning, Pr 5220 instrument manual

Advertising
background image

Commissioning

PR 5220 Instrument Manual

EN-102

Sartorius

4.8

Configuring Limit Values

Each limit value consists of a switch-on and a switch-off point for definition of a hysteresis. The three pairs of
values must be entered according to the same principle. The limit values always refer to the gross weight.

The limit values of an xBPI weighing point are scale-specific.
-

The scale must be active when entering the limit values.

-

The scale and the unit must not be changed after configuration.

-

The following settings are required:

[Weighingpoint/xBPI-Scale]-[Setup]-[Configuration]-[Application settings]-
[Number of units]: [1 Weight]

Define the limit values under

-[Limit parameter].

Press

to select the specific items.

Press

to select the respective parameter.

Setup/

Limit parameter

Determine the limit values.

Limit 1 on

890 kg

Action

-no action-

Limit 1 off

900 kg

Action

-no action-

Limit 2 on

300 kg

Action

-no action-

Limit 2 off

290 kg

Action

-no action-


Advertising