1 adapting the analog output, Adapting the analog output, Pr 5220 instrument manual commissioning – Rice Lake PR5220 Ethernet Transmitter User Manual

Page 111

Advertising
background image

PR 5220 Instrument Manual

Commissioning

Sartorius

EN-111

4.10.1

Adapting the Analog Output

The output current can be adapted in small ranges. This is required, if small deviations from the nominal value
occur in a connected PLC.

Open the menu with

[Show HW-slots]:

Info/

HW-Slots

Builtin

RS485

Builtin

analog out

Builtin

digital i/o

Select [analog i/o].

Info/

HW-Slots

Builtin

analog out

In use by PLC task

1

Analog output

4.004 mA

counts

10934 cnt

Stop PLC Stop I/O

Adjust

Reset

Press [Adjust].


Adapt analog output ?

Safety prompt: Reply [Yes] to start adapting.

Info/HW-Slots/

Adjust Analog Output

Output

4.000 mA

Measured

4.004 mA

Enter e.g. the value for 4 mA measured by the connected PLC under [Measured].
After pressing , the 2nd value (20 mA) is displayed:

Info/HW-Slots/

Adjust Analog Output

Output

20.000 mA

Measured

20.010 mA

Enter e.g. the value for 20 mA measured by the connected PLC under [Measured].