PR 5220 Instrument Manual

Fieldbus Interface

Sartorius

EN-141

7.4

Fieldbus Register

Register 0: I/O Status Bits for Reading
Dynamic status, only reading is permitted

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Byte 0

Input 3

Input 2

Input 1

Byte 1

Output 3 Output 2 Output 1

Byte 2

Limit 3

Limit 2

Limit 1

Byte 3

Register 1: Scale Status
Dynamic status, only reading is permitted

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Byte 0

DIM

STND

INZSR

CZERO

BELOW0

OVL

>Max

ADCERR

Byte 1

E6

E1

E3

E7

Byte 2

PowerFail

ActionActive

CmdError

Byte 3

TareActive

CalActive

TestActive


Byte 0 corresponds to byte 7 in the output area; for weight error, see also the table in Chapter 13.1.

ADCERR

Error of analog conversion/ load cell circuit (OR function of the E1, E3, E7 bits)

>Max

Gross value is higher than Max (maximum capacity); the full scale deflection was exceeded.

OVL

Scale overload; Gross >Max + overload,

Error 2

BELOW0

Gross weight is negative (<0-¼ d)

CZERO

Center of zero; weight within 0

±

¼ d

INZSR

The gross weight is within the zero setting range

STND

The scale is stable

DIM

The gross weight has exceeded the full scale deflection (0-¼ d > weight value >Max+overload),
(OR function of bits BELOW0, OVL).

E7

The input signal is negative (inverse conversion)

,

Error 7

E6

No sense voltage, or Sense voltage is low,

Error 6

E3

The input signal is >36mV (no end of conversion),

Error 3

E1

Arithmetic error (overflow),

Error 1

E9

No Communication with xBPI scale,

Error 9

CmdError

Error during execution (cmdError); e.g. the 'taring' operation is not handled, because the scale
is not stable. The error is stored in LastError (register 4). The bit is reset with the ResetError bit
(register 2).

ActionActive The operation is handled; handling is busy
PowerFail

Power failure; is always set after power on. The PowerFail bit is reset with the ResetPWF bit
(register 2) 'Reset power failure'.

TestActive

The analog test is busy

CalActive

The instrument is / was configured. When this bit is 1, the scale parameters (Expo/Unit/Step)
must be read again. Set after power On and reset after reading the max. capacity.

TareActive

The instrument was tared.