PR 5220 Instrument Manual
Commissioning
Sartorius
EN-97
SMA Protocol
Select an RS-485 interface under
-[Serial ports parameter].
Setup/
Serial ports
Remote display
none
SMA
Builtin RS485
Click [Param].
Param
Only the baud rate is adjustable; the other parameters are fixed.
Setup/Serial ports/
Builtin RS485
Assigned to
SMA
Baudrate
9600 bd Press
to select [Baudrate] and
Bits
8
set the baud rate with
.
Parity
none
Stopbits
1
The SMA protocol is described in Chapter 4.8.
xBPI-Protokoll
To configure the serial interfaces, press
-[Serial ports parameter]-[ xBPI-Port] to select a RS-485 interface.
Setup/
Serial ports
Remote display
-none-
SMA
-none-
xBPI-Port
Builtin RS485
Click [Param].
Param
Only the baud rate and the stop bits are adjustable; the other parameters are fixed.
Setup/Serial ports/
Builtin RS485
Assigned to
xBPI-Port
Baudrate
9600 bd Press
to select [Baudrate] and
Bits
8
set the baud rate with
.
Parity
odd
Stopbits
1 1, 2