Description of the i/o area (read / write window), Fieldbus interface, Pr 5220 instrument manual – Rice Lake PR5220 Ethernet Transmitter User Manual

Page 136

Advertising
background image

Fieldbus Interface

PR 5220 Instrument Manual

EN-136

Sartorius

7.2

Description of the I/O Area (Read / Write Window)

Input Area
Data transmission from the master to the PR 5220 (slave) is via the input area.
Weight or data requests are transmitted to the slave by the master.
The master has write access; the slave has read access.

Byte

Name

Description

0

Write_Value (MSB)

e.g. limit value

1

:::

"

2

:::

"

3

Write_Value (LSB)

"

4

Read_Value_Select

e.g. gross weight

5

Write_Value_Select

Write:

Limit 1 On

6

free

Res M 3 Res M 2 Res M 1 free

Set M 3 Set M 2 Set M 1

Reset/set marker

7

Get

FixTare

Set

FixTare

Res

Power

Res

Test

Set

Test

Res

Tare

Set

Tare

Set

Zero

Control byte,

response to

0->1

transition

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0


The

control byte

activates the corresponding action in the instrument with a set bit.

After execution of the operation, the bit should be reset.

Variable

Function

Write_Value

The weight value is transmitted as a binary 32-bit value with plus or minus sign.
Data type:

DINT

Read_Value_Select

For selecting the value sent by the instrument

Write_Value_Select

For selecting the function to be executed by the instrument

Res M 1…3

Reset marker 1…3.

Set M 1…3

Set marker 1…3.

GetFixTare

The gross weight is copied into the fixtare memory.

SetFixTare

Taring is performed using the value stored in the fixtare memory.

ResPower

The

Power_Fail

bit in the output area is deleted.

ResTest

The test operating mode is finished.

SetTest

The test operating mode is started. Now the test value can be read out by reading
out the gross weight.

ResTare

Tare is reset.

SetTare

The scale is tared.

SetZero

The scale is set to zero.

Advertising