Commissioning

PR 5220 Instrument Manual

EN-110

Sartorius

4.10

Analog Output

Determine the analog output under

-[Analog output parameter].

Setup

Serial ports parameter

Operating parameter

Fieldbus parameter

Network parameter

Weighingpoint

Limit parameter

Digital i/o parameter

Analog output parameter

Press

and

to select [Analog output parameter]

Setup/

Analog output parameter

Analog mode

no output

Analog range

0 ... 20 mA

Output on error

0 mA

Output if < 0

0 mA

Output if > Max

20 mA

Weight at 0/4 mA

0 kg

Weight at 20 mA

3000 kg

[Analog mode]

[no output]

The analog output is not used

[Gross D08]

Output of the gross weight

[Net D09]

Output of the net weight

[Select D11]

Output of the value on the display

[Transparent D30]

Output of the value in D30

[Analog range]

[0...20 mA]

Output of 0... 20 mA

[4...20 mA]

Output of 4... 20 mA

[Output on error]

[0 mA]

Set the output to 0 mA

[4 mA]

Set the output to 4 mA

[20 mA]

Set the output to 20 mA

[hold]

The last output value is held

[Output if < 0]

[0 mA]

Set the output to 0 mA

[4 mA]

Set the output to 4 mA

[20 mA]

Set the output to 20 mA

[linear]

The output drops below 4 mA up to the limitation (at 4 .. 20 mA)

[Output if > Max] [0 mA]

Set the output to 0 mA

[4 mA]

Set the output to 4 mA

[20 mA]

Set the output to 20 mA

[linear]

The output exceeds 20 mA up to the limitation

[Weight at 0/4 mA]

Weight value for 0/4 mA output

[Weight at 20 mA]

Weight value for 20 mA output

Press

to return to the previous menu.