Commissioning

PR 5220 Instrument Manual

EN-60

Sartorius

4.4.5

Determining the Dead Load

Note:

If the liniarization is active (see Chapter 4.4.10):
After selection of the line ‚Dead load at’ the following tip is displayed:

Can not be changed here

while linearization is active

Weighingpoint/WP A/

Calibration

Max

3000 d

3000 kg

Scale interval

3000 d

1 kg

Deadload at

0.00 kg

0.000000

Max at

3000.00 kg

1.000000

Not calibrated

Sensitivity

833.33

4.000000

by load

by mV/V

CalcTest

To use the empty scale/hopper as dead load (normal case):
• discharge the scale/hopper
• press [by load]
After

or confirmation of the change is displayed:

Set deadload

If the mV/V value of the dead load was calculated, or if it is known from the previous calibration, the value can
be overwritten by pressing [by mV/V].

Weighingpoint/WP A/

Calibration

Max

3000 d

3000 kg

Scale interval

3000 d

1 kg

Deadload at

0.00 kg

0.000000

Max at

3000.00 kg

1.000000

Calibrated at

3000.00 kg

1.000000

Sensitivity

833.33

4.000000

by load

by mV/V

CalcTest