9272000990 Rev J

BE1-BPR Functional Description

4-49

CAL

Calibration values

HMI Menu Branch: 5 (Standard), 6

(Enhanced)

Parameter

Parameter Selections

Comments

amps

1 ampere units:
2 (low range)
8 (high range) ∗
5 ampere units:
10 (low range)
40 (high range) ∗

After calibration, the calibration

results are reported as “CAL OK” or

“CAL FAIL <reason for failure>”.
Entering CAL by itself will return the

calibration values for each

calibration range and phase. The

calibration values represent the

number of A/D bits per ampere for

each current input.

High range values are to be used only with enhanced units.


CAL HMI Screen Example:

CAL Command
Purpose:

Read or change calibration values.

Syntax:

CAL[x][=<amps>]

Comments:

x = 1 (low range, 2 (high range)

Access area one password is required to make calibration changes.


CAL Command Example:
Read the relay calibration values.

CAL

CAL1A=140.766; CAL1B=141.110; CAL1C=143.237; CAL1N=141.543

CAL2A=7.076; CAL2B=7.070; CAL2C=7.083; CAL2N=7.064

FREQ

Power system frequency

HMI Menu Branch: 5 (Standard), 6

(Enhanced)

Parameter

Parameter Setting

Default

freq

50 or 60

60

FREQ HMI Screen Example:

FREQ Command
Purpose:

Reads or changes the nominal power system frequency information used by the relay.

Syntax:

FREQ[=<freq(hz)>]

Comments:

Access area password one is required to change the setting.


FREQ Command Examples:
1. Read the frequency setting.

FREQ

60
2. Change the frequency setting to 50 hertz.

FREQ=50

CAL FREQ

RANGE-1L/2H 60

CAL FREQ

RANGE-1L/2H 60