Current Sensing
Four isolated inputs with a maximum burden of less than 0.1 ohm.
5 Ampere CT:

Maximum continuous current: 20 Aac

Maximum one second current: 500 Aac

1 Ampere CT:

Maximum continuous current: 4 Aac

Maximum one second current: 80 Aac

Current Detector Pickup Time

1 ¼ cycle maximum for current 125% greater than pickup.

Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3)

Maximum pickup time is (Window_size/C_PM + 1 ¼ (cy)), where Window_size = Filter window size in

cycles (Range 1 - 100) and C_PM = Current Pickup Multiple

Moving Average Window Fault Detector (50/60 Hz RMS Filter Type 2)

Current Detector Dropout Time

Dropout/pickup ratio: 90%, typical. One-quarter cycle (4.2 milliseconds @ 60 hertz) from the time the

current falls below and stays below 25% of the RMS level or 1 ¼ cycle from the time the RMS current

signal decreases to less than 75% of pickup.

Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3)

Maximum dropout time is (Window_size-(Window_size/C_PM) + 1 ¼ (cy)), where Window_size = Filter

window size in cycles (Range 1 - 100) and C_PM = Current Pickup Multiple level before dropout.

Moving Average Window Fault Detector (50/60 Hz RMS Filter Type 2)

Current Pickup Range
Three independent settings, selectable as three-phase or neutral.

5 ampere CT:

0.25 to 9.99 amperes selectable in 0.01 increments

Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3)

1 ampere CT:

0.05 to 2.00 amperes selectable in 0.01 increments

5 ampere CT:

0.05 to 1.00 amperes selectable in 0.01 increments

Moving Average Window Fault Detector (50/60 Hz RMS Filter Type 2)

1 ampere CT:

0.01 to 0.20 amperes selectable in 0.01 increments

Current Pickup Accuracy

5 ampere CT:

±

2% of pickup setting or ±0.05 Aac (whichever is greater)

Instantaneous Fault Detector (50/60 Hz RMS Filter Type 1 and 3)

1 ampere CT:

±

2% of pickup setting or ±0.01 Aac (whichever is greater)

5 ampere CT:

±

25% with window of 10 cycles or larger

Moving Average Window Fault Detector (50/60 Hz RMS Filter Type 2):

1 ampere CT:

±

25% with window of 10 cycles or larger

Sample Rate
12 samples per cycle (720 samples per second at 60 hertz, 600 samples per second at 50 hertz).

Oscillograph Recording Range
5 ampere CT:

0 - 200 amperes, rms

1 ampere CT:

0 - 40 amperes, rms

Oscillograph Data Accuracy
±

0.2% of full scale or 5% of reading, whichever is greater