4-18

BE1-BPR Functional Description

9272000990 Rev J

LF

Fault detector logic

HMI Menu Branch: N/A

Parameter

Parameter Selections

Defaults

type

PI (phase overcurrent)

NI (neutral overcurrent)

LF1=PI,1

LF2=NI,1

LF3=PI,2

filter

1 (1cycle RMS filter)

2 (moving average filter)

3 (1 cycle RMS 3-phase filter


LF Command
Purpose:

Read or change the fault detector logic of the active logic scheme.

Syntax:

LF[x][=<type>,<filter>]

Comments:

An access area one password is required to change settings.


LF Command Examples:
1. Program fault detector 1 as a phase overcurrent fault detector using digital filter 1.

LF1=PI,1

2. Program fault detector 2 as a neutral overcurrent fault detector using digital filter 1.

LF2=NI,1

3. Program fault detector 3 as a phase overcurrent pickup using the moving average filter (filter 2).

LF3=PI,2


The PU command sets the trip value of each fault detector and the moving average filter cycles for type 2

fault detectors.

CAUTION

A pickup setting range check is made each time logic settings are changed that

affect the fault detector pickup settings. For example, if PU1=5.00 and LF1

setting is changed from PI,1 to PI,2, the PU1 setting will automatically change

from 5.00 to 1.00 (the maximum allowable setting for a Type 2 fault detector on a

5 A unit). This kind of pickup setting adjustment can also occur if the active relay

logic is replaced with logic that has different LF settings.