Breaker arc detector, Breaker arc detector -9, Figure 2-11. trip circuit monitor with bfi sensing – Basler Electric BE1-BPR User Manual

Page 33

Advertising
background image

9272000990 Rev J

BE1-BPR Application

2-9

Figure 2-11 illustrates a problem that can occur when using the trip circuit monitor feature. If the breaker

failure initiate (BFI) sensing is connected directly to the breaker trip bus as shown in Figure 2-11a, the

equivalent circuit shown in Figure 2-11b occurs. If the diode of the circuit is not included, a voltage divider

circuit will be created between the BFI sensing and the TCM sensing when the 52a contact or the trip coil

is open.

Figure 2-11. Trip Circuit Monitor with BFI Sensing


In Figure 2-11a, a 62x BFI auxiliary relay is shown. In this case, the impedance of the 62x coil will be

small compared to the impedance of the TCM circuit so the TCM will always be at logic 1. This will

prevent the TCM logic from working, even if the trip coil is open. In the case that the high impedance BFI

sensing input of the BE1-BPR is connected directly to the trip bus, the TCM and the BFI impedances will

be of similar magnitude causing the voltage to be divided nearly equally. This can result in spurious BFI

signals to the breaker failure protection scheme when the breaker is open. Normally, when redundant

systems are used, each relay system will be on its own circuit and the BFI sensing for each relay system

will be isolated from the tripping circuit so this is not a problem.

Breaker Arc Detector
Once a breaker is open, an arc or flashover from a lightning strike may occur if the surge suppressors fail

or air pressure is lost in an air blast circuit breaker. If this arc is not extinguished, the breaker can be

damaged or destroyed. If the breaker was opened due to a fault on the line, then protective relays on the

line will operate. If the line is not cleared, the relay logic will trip the backup breakers to clear the line and

save the breaker.
If both ends of the line are open with no fault, then the breaker may just be carrying low level, line

charging current. This current will not operate the protective relays because it is well below the normal

loading levels. However, it is enough to destroy the breaker if not cleared. To provide protection for this

situation, a very sensitive fault detector is needed that operates at line charging current levels and is only

enabled when the breaker is open. When the fault is detected, the arc can be cleared by reclosing the

breaker or operating backup protection for breaker failures. Reclosing will not affect safety of personnel if

normal working practices are followed to disconnect any sections of the line being worked on (the line

would be energized by the arc in any case). If the breaker reclosed into a faulted line, the normal

protection devices would immediately re-open the line.
The BE1-BPR relay has a sensitive low level pickup for this application (MAF fault detector). Figure 2-12

shows the breaker arc detector circuits with the three-phase MAF fault detector (F3). It is easy to inhibit

the relay based on the breaker status by programming the relay logic. As discussed previously in the fault

detector application paragraphs, the MAF fault detector filter is slow to pickup and dropout. Therefore, the

fault detector response must be delayed to allow time for normal load or fault current to clear the filter

section. For example, if a 60 cycle MAF fault detector is used and set at 0.1 ampere (below line charging

current levels), then the MAF fault detector remains picked-up for 1 second after the breaker opens

because it takes that long for the filter buffer to clear. Therefore, the MAF fault detector output must be

delayed for a time longer than the filter length to ensure that only a sustained current signal causes an

output. This delay time could be 20 to 30 seconds longer.

52a

N

P

T

BFI

or

62X

TCM

+

V

-

+

V

-

86

Breaker

Retrip

O5

IOIT

21

IN2 (TCM)

Trip Ckt 1

Sense

P

T

52a

52TC1

N

62X

a. Schematic Diagram

b. Equivalent Voltage

Divider Circuit

D

28

22

-0

9

08

-0

7-

98

Advertising