Radio frequency interference (rfi), Temperature, Shock – Basler Electric BE1-BPR User Manual

Page 21: Vibration, Gost-r certification, Weight, Radio frequency interference (rfi) -9, Temperature -9, Shock -9, Vibration -9

Advertising
background image

9272000990 Rev J

BE1-BPR General Information

1-9

Radio Frequency Interference (RFI)
Field tested using a 5 W, hand-held transceiver operating at random frequencies centered around 144

MHz and 440 MHz, with the antenna located six inches from the relay in both horizontal and vertical

planes.

Temperature
Operating:

-40°C to +70°C (-40°F to +158°F)

Storage:

-40°C to +70°C (-40°F to +158°F)

Shock
Type tested to withstand 15 G in each of three mutually perpendicular planes, swept over the range of 10

to 500 Hz for a total of 6 sweeps; 15 minutes each sweep, without structural damage or degradation of

performance.

Vibration
Type tested to withstand 2 G in each of three mutually perpendicular planes, swept over the range of 10

to 500 Hz for a total of 6 sweeps; 15 minutes each sweep, without structural damage or degradation of

performance.

Gost-R Certification
Gost-R certified, No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of

Russia. Issued by accredited certification body POCC RU.0001.11ME05.

Weight
12 lb (5.44 kg) maximum

Advertising