4-24

BE1-BPR Functional Description

9272000990 Rev J

Recloser Outputs. There is a CLOSE output on O13 and diagnostic status flags for reclose fail and

lockout. Output O13 and the diagnostics for reclose fail and lockout can be programmed to drive output

relay contacts by using the LO and PDIAG commands.
The function of each output or flag is defined as:
CLOSE:

The reclose output contacts close at the end of each reclose time delay. They open

when the RESET input shows that the breaker has closed, when the reclose fail timer

times out, or when the recloser goes to LOCKOUT or the WAIT input is asserted.

RECLOSE FAIL: The reclose fail diagnostic flag is set when the reclose fail timer times out and

remains set until the recloser goes to the reset state.

LOCKOUT:

The lockout flag is set when the recloser goes to LOCKOUT and remains set until the

recloser goes to the reset state. The recloser goes to LOCKOUT if more than the

maximum number of shots programmed is initiated before the recloser returns to the

reset state, if the Drive to Lockout (DTL) input is true, or if RECLOSE FAIL is true.

Reclosing Mode (TYPE). Reclosing mode controls the reclosing sequence on powerup. There are three

modes of operation and one is selected by setting the TYPE in the LR command to 0, 1, or 2.

TYPE 0 disables the reclosing function.
TYPE 1 requires that after power-up, the RESET input logic stay true for the reset time delay (TD79R) or

the recloser automatically goes to LOCKOUT.
TYPE 2 allows the recloser to initiate the first programmed reclose operation after power-up if power was

lost when the recloser was in the reset state and at power-up, the RESET logic is false and the START

logic is true. If RESET goes true and stays true for the reset time delay (TD79R), the recloser

automatically goes to RESET. This type of reclosing mode may be appropriate if the BE1-BPR relay is

powered-up from the station service.
Recloser Operation. There are a maximum of three reclose shots, each with a programmable time delay.

The three time delays can be set from 10 to 999 milliseconds in 1 milliseconds increments, 1 to 99

seconds in 0.1 second increments, or 100 to 600 seconds in 1 second increments. A setting of zero for

reclose shot 1, 2, or 3 will send the relay to lockout when that reclose shot is reached in the reclosing

sequence.
If the recloser is in the reset state upon receiving a START input signal (RI) and RESET is false (52a or

/52b), the reclose logic issues a reclose output (O13). The output occurs after the TD791 time delay

setting. If the breaker closes and then opens again before the reset timer is timed out, a reclose output

occurs after the second time delay. The third reclose output occurs in a similar manner. The recloser goes

immediately to the lockout state on the fourth breaker trip.
Reset timer (TD79R) begins timing out when the RESET logic becomes true (breaker closes). The reset

timer is reset when the breaker trips. If the reset timer times out while the breaker is closed, the recloser

goes to the reset state. Setting the reset time delay at zero will give an instantaneous reset and eliminate

reclose shots 2 and 3 from the reclose sequence.
If enabled, the reclose fail timer (TD79F) starts whenever a reclose output is given and stops when the

RESET logic indicates the breaker has closed. It is used to limit the duration of the reclose output signal.

If the reclose fail timer times out before the RESET logic becomes true, the recloser sets the reclose fail

diagnostic flag. The reclose fail function can be inhibited by setting the RECLOSE FAIL time delay

(TD79F) to zero (0).
If the total reclosing time between reset states exceeds the maximum reclose cycle timer (TD79M) setting

(excluding time while in the WAIT state), the recloser goes to the lockout state. The lockout alarm

diagnostic flag is set whenever the recloser goes to the lockout state. A time delay setting of zero will

inhibit the maximum reclose timer functions.

NOTE

After the programmable logic is changed or the time delay settings are changed,

the recloser initializes as described in the Reclosing Mode, TYPE 1 or TYPE 2.