BE1-BPR Functional Description

4-25

Output Hold Function
Protection outputs will usually have a minimum hold time to ensure that the protective relay contact does

not interrupt the trip coil current and the breaker close output will stay closed until the recloser shows that

the breaker has closed. The PHOLD command provides a 200-millisecond output hold time that can be

enabled or disabled for each output.

PHOLD

Output hold timers

HMI Menu Branch: N/A

Parameter

Parameter Selections

Defaults

#####

0 = no minimum hold time

1 = 200 ms minimum hold time

Each digit of the PHOLD parameter

represents an output. The leftmost

digit represents OUT1. The right-

most digit represents OUT5.

Typically, the 200 millisecond hold

time will be enabled for all outputs

except those used for reclosing.

PHOLD Command
Purpose:

Read or program the output hold timer mask.

Syntax:

PHOLD [=<#####>]

Comments:

Access area password 1, 2, or 3 required to change settings. Default setting is 11111.


PHOLD Command Example:
Disable the minimum hold time for output 3. Enable the minimum hold time for outputs 1, 2, 4, and 5.

PHOLD=11011

Relay Status
For diagnostic purposes, the RELAY STATUS menu screen provides a means of checking the status of

the current inputs, contact sensing inputs, output contacts, recloser, and relay diagnostics. This informa-

tion can also be obtained using the STATUS, I, and DIAG commands.
Typical RELAY STATUS screens are shown below on the left. An example of a report obtained using the

STATUS command is shown below on the right.

RELAY STATUS

menu screen

IA=3.00KA; IB=3.00KA

IC=3.00KA; IN=0.00KA

I (1-7) = 0100000

T (1-6) = 000000

F (1-3) = 001

O (A,1-15) = 0000000000000000

RECLOSER RESET

BREAKER CLOSED

DIAG: 1 to 1 TIMER ALARM

Sub-screen 1 Input

and Output Contact

Status

Sub-screen 2

Primary Current

Metering Values

Sub-screen 3

Secondary Current

Metering Values

Sub-screen 4

Recloser Status

Sub-screen 5+

Diagnostic

Message Screen(s)

DIAG: NONE

RECLOSER RESET

Ia=2.13 Ib=2.13

Ic=2.13 In=0.00

IA=1.28K IB=1.28K

IC=1.28K IN=0.00K

I1234567 OA12345

0000000 000000

RELAY STATUS