BE1-BPR Functional Description

4-51

OUT Command
Purpose:

Pulses outputs on or off for testing purposes.

Syntax:

OUT[x=<1/0>/DISABLE]

Comments:

x = A (OUTA, 1 (OUT1), 2 (OUT2), 3 (OUT3), 4 (OUT4), or 5 (OUT5)

Entering OUT=1 or OUT=0 will pulse on or pulse off all outputs.

Access area one or four password is required to test outputs.


OUT Command Examples:
1. Enable the output test feature.

ACCESS=<password> (access area 1 or 4 password)

OUT=ENABLE;SAVE;Y

2. Test output 1 by closing it momentarily.

ACCESS=<password> (access area 1 or 4 password)

OUT1=1

When testing complete, disable the OUT command by entering OUT=DISABLE;SAVE;Y

The firmware version may be viewed on the front panel HMI and through the communications ports.

When power is first applied to the relay, the firmware version is briefly displayed on the front panel LCD.

The firmware version can also be viewed at HMI Maintenance menu sub-screen 6. These screens are for

viewing only; the displayed firmware version cannot be altered.

Firmware Version Display

The VER command will return the software version number as well as the relay model, part, and serial

number.

VER

Relay version information

HMI Menu Branch: 5 (Standard), 6

(Enhanced)

Comments
This command returns the relay model number, the program version number, the relay part

number, and the relay serial number.


VER HMI Screen Example:


VER Command
Purpose:

Returns information about relay hardware and software.

Syntax:

VER

Comments:

No access area password is required for reporting functions. Version information

provided through HMI is limited to the relay model number and software version number.


VER Command Example:
Obtain the program version, part number, and serial number of the relay.

VER

Model : BE1-BPR

Program : VER 3.29E

PN : 9 2720 00 301

SN : H12345678

MODEL: BE1-BPR

PROGRAM: VER X.XX