General purpose timers, Delay timer, General purpose timers -5 – Basler Electric BE1-BPR User Manual

Page 29: Figure 2-5. multiple breaker arrangement, Figure 2-6. delay timer operation

Advertising
background image

9272000990 Rev J

BE1-BPR Application

2-5

Low Level Current Detector. If the breaker fails while being opened for normal load switching or due to re-

strike after the line has been isolated, the currents flowing across the failed interrupter may be too low to

reliably detect by conventional means. The Type 2 fault detector’s moving average filter allows the BE1-

BPR to discern the low level line charging current from random noise. The application of this fault detector

is described in detail in the Breaker Arc Detector sub-section. Fault detector F3 is programmed as a

phase MAF fault detector in all pre-programmed logic schemes.
Multiple Breaker Arrangements. In ring bus and breaker and half bus applications, CTs from two breakers

are often connected in parallel. If the BE1-BPR is connected to these CTs as shown in Figure 2-5, low

fault detector pickup settings should be used with caution. In this arrangement, the CT feeding the BE1-

BPR can be energized on the secondary side from the CT on the adjacent circuit breaker. This results in

current flowing in the BE1-BPR even when the protected circuit breaker has successfully interrupted the

fault. This secondary excitation current is generally negligible except when flux remnants or high

current/burden causes the CT to saturate.

Figure 2-5. Multiple Breaker Arrangement

General Purpose Timers
Each BPR relay provides six independent timers for breaker failure timing and diagnostics. Each timer

can be programmed as a delay or a control timer and can have independent START and RESET

conditions. Each timer can also provide a diagnostic log and/or alarm. These features are explained in the

following paragraphs.

A Delay timer has two inputs START and RESET, and one output T[n]. The timer will not start until the

start condition becomes TRUE and the RESET input is FALSE. Once the timer is started, a pre-

programmed time delay, TD[n], is loaded and the timer starts timing out. Toggling of the START input has

no effect once the timer is started. The timer times out TD[n] time after the timer is started unless the

timer is RESET before the time expires. If the timer times out, then the T[n] output becomes TRUE. After

timeout, T[n] remains TRUE until the timer is RESET. Delay timer operation is illustrated in

Delay Timer

Figure 2-6.

Figure 2-6. Delay Timer Operation

INITIATE

OUTPUT

RESET

TD[n]

D2635-11

Advertising