BE1-BPR Installation

9272000990 Rev J

Each BE1-BPR is delivered with the contact sensing jumpers installed for operation in the lower end of

the control voltage range. If the contact sensing inputs are to be operated at the upper end of the control

voltage range, the jumpers must be changed or removed. Table 7-1 lists the turn-on voltage range for

each control voltage range and jumper position.
The contact sensing jumpers are used to select the lower or upper sensing range for each contact input

circuit. These jumpers ensure that the input will be off below 55 percent of nominal battery voltage and on

above 80 percent of nominal battery voltage.

Table 7-1. Contact Sensing Turn-On Voltage

Nominal Control Voltage

Turn-On Range

Pin 1 - Pin 2

Pin 2 - Pin 3

48/125 Vac/Vdc

26 to 38 V

69 to 100 V

125/250 Vac/Vdc

69 to 100 V

138 to 200 V


The following paragraphs describe how to locate and remove or change the contact sensing input

jumpers.
1. Remove the drawout assembly by rotating the two captive, front panel screws counterclockwise and

then sliding the assembly out of the case. Observe all electrostatic discharge (ESD) precautions

when handling the drawout assembly.

2. Locate the seven jumper terminal blocks (JP200 through JP206) that are mounted on the Logic

Circuit Board. The jumper terminal blocks are located on the component side of the circuit board near

the left hand side (right-hand side when looking at the unit from the rear). Each terminal block has

three pins and each jumper is installed at the factory on pins 1 and 2. Figure 7-10 illustrates the

location of jumpers placed for operation in the lower end of the control voltage range.

3. To select operation at 125 Vdc, remove the jumper entirely from the unit or position it on pins 2 and 3.
4. When all jumpers are positioned for operation in the desired sensing voltage range, prepare to place

the drawout assembly back into the case.

5. Align the drawout assembly with the case guides and slide the assembly into the case.
6. Rotate the two captive front-panel screws clockwise to secure the drawout assembly in the case.