5-18

BE1-BPR BESTlogic Programmable Logic

9272000990 Rev J

CUSTOM APPLICATION EXAMPLES

Breaker Failure Logic for Breakers with Pre-Insertion Resistors (BFRES)
BFRES logic is an example of an adaptive breaker resistor protection scheme that allows more time for

the fault to clear once the breaker resistor has reduced the fault current. For more information, refer to

Section 2, Breaker Failure Protection with Pre-Insertion Resistors.

Figure 5-10. BFRES Logic Diagram



LN=BFRES

LI6=4,12

LOA=T4+O15 ∗

LO9=0

LF1=PI,1

LI7=4,12

LO1=T1O7+T2F3

LO10=0

LF2=NI,1

LR=0,0,0,0,0

LO2=T1O7+T2F3

LO11=0

LF3=PI,2

LT1=D,O8,/O8

LO3=T1O7+T2F3

LO12=F3I1

LI1=4,12

LT2=D,O8,/O8

LO4=O14

LI2=4,12

LT3=0,0,0

LO5=O8

LI3=4,12

LT4=D,O6,/O6

LO6=/I1/I2

LI4=4,12

LT5=0,0,0

LO7=F1+F2

LI5=4,12

LT6=0,0,0

LO8=I3+I4+I5


The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.