9272000990 Rev J

BE1-BPR General Information

1-7

Timer Accuracy
Standard (TD[n]):

+4 and -1 milliseconds ±0.01% of setting

Reclosing (TD79[n]):

+20 and -1 milliseconds ±0.01% of setting

Real Time Clock Set Ability
±

1 second

Real Time Clock Resolution
±

1 second

Real Time Clock Stability
±

30 ppm typical

Real Time Clock Accuracy
Relays with IRIG, ±1 millisecond. If IRIG signal is lost, accuracy defaults to the real time clock stability.

BESTlogic Operate Time
Operate time is 1.4 milliseconds typical, 2.8 milliseconds maximum at 60 hertz.

Output Relays
Any output contact closed by the relay logic will be held closed for 200 to 250 milliseconds even if the

initial cause of the closing goes away. After 200 to 250 milliseconds, the relay close time is determined by

the state of the relay logic. This minimum hold time may be disabled by using the PHOLD command.
Factory Presets

ALARM Output:

Output contacts close when ALARM logic (LOA) is true or power is lost.

Outputs 1 - 5:

Output contacts close when the corresponding logic equation (LO1 -

LO5) is true.

Pickup Time (All models except 9272000328, 9272000329, 9272000330, and 9272000331)

ALARM:

8 milliseconds typical, 10 milliseconds maximum

OUTPUT 1:

4 milliseconds typical, 5 milliseconds maximum

OUTPUT 2, 3, 4, 5:

8 milliseconds typical, 10 milliseconds maximum

Pickup Time (Models 9272000328, 9272000329, 9272000330, and 9272000331 only)

ALARM:

8 milliseconds typical, 10 milliseconds maximum

OUTPUT 1, 2:

4 milliseconds typical, 5 milliseconds maximum

OUTPUT 3, 4, 5:

8 milliseconds typical, 10 milliseconds maximum

Resistive Ratings

120 Vac:

Make, break, and carry 7 Aac continuously

250 Vdc:

Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,

break 0.3 Adc

500 Vdc:

Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,

break 0.3 Adc

Inductive Ratings

120 Vac, 125/250 Vdc:

Break 0.3 A (L/R = 0.04)

Display
Two-line, 16 character alphanumeric LCD (liquid crystal display) with LED (light emitting diode) backlight.
Operating Temperature:

-40°C to +70°C (-40°F to +158°F)

Display contrast may be impaired at temperatures below -20°C (-4°F).