Figure 4-11. margin log timing sequence, Figure 4-12. margin log logic – Basler Electric BE1-BPR User Manual

Page 89

Advertising
background image

9272000990 Rev J

BE1-BPR Functional Description

4-37

Figure 4-11. Margin Log Timing Sequence

Figure 4-12. Margin Log Logic

PTLOG

Timer log and alarm log

HMI Menu Branch: N/A

Parameter

Range

Comments

logic term

N/A

AND and NOT(/) logic variables can be used to

specify when timer log is triggered.

alm_type

H, L, or 0

H: Alarm occurs when the remaining time at the

point the timer logic becomes true is higher than

the alarm_time setting.
L: Alarm occurs when logic becomes true inside

the alm_time margin.
0: Disables the alarm function.

alm_time

0 - 65 seconds

A diagnostic alarm is logged if logic becomes

true inside (alm_type L) or outside (alm_type H)

this time window. alm_time units can be

milliseconds (default), seconds (s), or cycles (c).

Figure 4-13 illustrates an example of an H alarm

and L alarm condition.

I2

TD1

100 msec.

25 msec.

O7

17:00:00.000

05/01/98

13 msec.

O7

18:00:00.000

05/01/98

ASCII TIMER LOG

TLOG1= 8m* 19:00:00.000 05/01/98

TLOG1= 13m 18:00:00.000 05/01/98

TLOG1= 25m 17:00:00.000 05/01/98

8 msec.

O7

19:00:00.000

05/01/98

D

26

35

-1

3

05

-0

5-

98

Advertising