Breaker operations counter, Breaker resistor diagnostics, Figure 4-10. output 13 logic – Basler Electric BE1-BPR User Manual

Page 86

Advertising
background image

4-34

BE1-BPR Functional Description

9272000990 Rev J

The breaker operations counter logs the number of open and close cycles of the circuit breaker. The

counter increments when the breaker closes. The number of breaker operations can be viewed or set

through the communications ports using the BKROPS command or through the HMI using Breaker Status

sub-screen 3. Breaker operations can also be viewed on the Breaker Status Menu Screen. The BKROPS

command also defines the logic for determining the breaker position (open or closed). Refer to the

Breaker Status Screen sub-section for information about using the BKROPS command.

Breaker Operations Counter

Breaker-opening resistors are used on some high voltage breakers to limit the maximum interrupting

current during fault conditions. This resistor is mechanically linked to the main breaker contact so that

when the main breaker contact opens, the opening resistor is placed in series with the phase current

approximately one-half cycle before the breaker opens. Since the breaker resistor is usually much larger

than the fault resistance, the breaker resistor will tend to limit the fault current to a value based on the

primary circuit voltage divided by the breaker resistor value ( Ires = V

LN

/ R ). This value, Ires, will be less

than the maximum short circuit rating (I

SC

) for the breaker.

Breaker Resistor Diagnostics

Typically, a breaker-opening resistor will be rated to allow a maximum number of operations (MAXOPS)

before waiting a defined reset or cooling off period. This reset period must occur before another operation

can safely be allowed. The BE1-BPR keeps track of the accumulated resistor heating by adding one

operation to the RESOPS counter for every breaker opening and subtracting one from the RESOPS

counter, <reset> minutes after the operation was logged.
The breaker resistor counter, RESOPS, stores in volatile memory the accumulated breaker operations

that are not reset. The current status of this counter is displayed on BREAKER STATUS menu,

sub_screen 2.
If reclosing is disabled and the accumulated operations equals MAXOPS, virtual output 13 (O13)

becomes true. This virtual output may be connected to an actual output by programming the logic. This

output contact can provide a block reclose output (BRO) to prevent another operation and overheating

the opening resistors. If the reclosing function is enabled, and the accumulated operations equals

MAXOPS, the block reclose signal is internally ORed with the defined WAIT logic input. This action delays

reclosing to protect the opening resistors from overheating. Figure 4-10 illustrates the logic that controls

virtual output 13 (O13) when breaker resistor protection and/or reclosing is enabled.

Figure 4-10. Output 13 Logic