Fault log (enhanced relays only), Fault log listing, Fault log (enhanced relays only) -39 – Basler Electric BE1-BPR User Manual

Page 91

Advertising
background image

9272000990 Rev J

BE1-BPR Functional Description

4-39

Fault Log (Enhanced Relays Only)
The fault log provides information about recent events that generated oscillograph data records. A record

is generated when the TRIGGER command logic expression becomes true. Events are numbered from 1

to 255 and are accessed in reverse chronological order (last in, first out). The number of an oscillograph

record corresponds to the number of the fault log. After fault log number 255 is recorded, fault log

numbering automatically starts over at fault log number 1. When the fault memory becomes full, the

oldest record is overwritten by the latest record acquired.

A list of fault log records can be viewed through the HMI menu screens or through a communications port

using the FLOG command. Each fault log listing shows the fault number, fault time and date, and the

protective elements that were active at the time the fault occurred. Examples of HMI and ASCII fault log

listings follow.

Fault Log Listing

FAULT LOG

menu screen

129 08:33:22.751 02/22/07, 50 TARGETS=A,N
128 08:33:09.796 02/22/07, 50 TARGETS=A,N
127 19:34:48.467 01/30/07, 50 TARGETS=A,N
126 14:25:09.663 12/20/06, 50 TARGETS=A,N
125 12:26:41.653 11/25/06, 50 TARGETS=A,N
124 11:19:19.684 11/01/06, 50 TARGETS=A,N
123 11:19:15.176 11/01/06, 50 TARGETS=A,N
122 12:08:23.488 10/09/06, 50 TARGETS=A,N
121 00:00:22.758 09/18/06, 50 TARGETS=A,N
120 23:55:09.896 07/22/06, 50 TARGETS=A,N
119 18:34:58.367 07/03/06, 50 TARGETS=A,N
118 13:25:06.613 05/20/06, 50 TARGETS=A,N

Sub-screen 1

Sub-screen 2

Sub-screen 10

FLOG

Fault log information.

HMI Menu Branch: 5

Parameter

Range

Comments

#

0: clears all fault records
1-255: provides summary

information about any one

of 255 fault records

Entering FLOG with no parameter will provide a

dated listing of the fault records stored in

memory.


FLOG Command
Purpose:

Reads a listing of all fault records, reads summary information about any individual fault

record, or clears all fault records.

Syntax:

FLOG[#][=0]

Comments:

This function is available on enhanced BE1-BPR relays only. No access area password s

required to read or reset fault log data.


FLOG Command Example:
Read fault log 125.
FLOG125

FAULT LOG #125

DATE = 11/25/07

TIME = 12:26:41.653

LOGIC=BFL1

I (1-7) =0111000

T (1-6) =100000

F (1-3) =111

120 23:55 7/22

50 TARGETS: AN

129 8:33 2/22

50 TARGETS: AN

129 8:33 2/22

50 TARGETS: AN

FAULT LOG (FLOG)