PROGRAMMING CUSTOM PROTECTION SCHEMES

Groups of commands can be saved to an ASCII text file and then uploaded as a group. However, care

should be taken to ensure that every command is terminated with either a carriage return or a semi-colon

and that the length for any line does not exceed 40 characters. Some common method of handshaking

must be enabled at both the relay and the computer uploading the commands. Handshaking such as

XON/XOFF (X1) or RTS/CTS (H1) should be used. Information about configuring handshaking can be

found in the Communication Settings sub-section of Section 4, Functional Description.

Customizing Preprogrammed Schemes
To customize a preprogrammed scheme, follow these steps:
1. Copy the preprogrammed scheme logic equations to custom memory by using the

LN=<preprogrammed_logic_name> command. All previous equations assigned to the custom logic

are overwritten with the equations from the preprogrammed logic scheme.

2. Rename the scheme to a unique, non-preprogrammed name by using the LN=<new_name>

command. This allows the scheme to be programmable.

3. Change the logic equations as needed using the LF, LI, LT, and LO commands. Any equations not

changed will be left as they were.

4. Review the changes using LINFO<new_name> or the LF, LI, LT, and LO commands.
5. If the new logic is to become the active logic, then type LOGIC=<new_name>.
6. Save the customized scheme using the SAVE command.

Example: Modify the pre-programmed BFL1A logic scheme so that breaker status is defined by the

52A contact instead of the 52B contact. Give this custom logic scheme the name of BFL1-25A. The

following commands change the equations that use the 52b logical input and rename the logic

scheme.
LN=BFL1
LN=BFL1-52A
LO6=I1/I2
LO12=F3/I1
LOGIC=BFL1-52A
SAVE;Y

Programming Custom Schemes
To program a new scheme, follow these steps:
1. Name the scheme with a unique, non-preprogrammed name by using the LN=<new_name>

command. This allows the scheme to be programmable.

2. Disable the outputs or function modules not needed by setting them equal to 0. (i.e. LO12=0). All

equations in a group can be programmed or disabled at once by not using a number.
Example 1: LI=8,12 changes all input logic to 8,12.
Example 2: LO=0 clears all output equations before writing new ones.

3. Change the logic equations using LINFO<new_name> or the LF, LI, LT, and LO commands.
4. Review the changes using LINFO<new_name> or the LF, LI, LT, and LO commands.
5. If the new logic is to become the active logic, then type LOGIC=<new_name>.
6. Use the SAVE command to save the customized logic scheme.