Figure 4-7. reclosing logic circuit – Basler Electric BE1-BPR User Manual

Page 74

Advertising
background image

4-22

BE1-BPR Functional Description

9272000990 Rev J

Figure 4-7. Reclosing Logic Circuit

TD79

Reclose timer delays ∗

HMI Menu Branch: 2

Parameter

Unit of Measure

Range

Increment

Default

delay

milliseconds (m)

seconds (s)

cycles (c)

10 - 999 ms

1 - 600 seconds

1 - 36014 (60 Hz)

1 - 30000 (50 Hz)

1 ms

0.1 s (1-100 s)

1.0 s (100-600 s)
1 cy

TD791=50m

TD792=1.0s

TD793=5.0s

TD79R=120s

TD79F=0m

TD79M=0m

All timer settings greater than or equal to 1 second are rounded to 0.1 second resolution.


TD79 HMI Screen Examples:

TD79 Command
Purpose:

Read or change recloser (79) time delay settings.

Syntax:

TD[x][=<delay>]

Comments:

x = the number of the timer being read or changed where:

1 = TD791, the reclose shot 1 time delay

2 = TD792, the reclose shot 2 time delay

3 = TD793, the reclose shot 3 time delay

R = TD79R, the reset time delay

F = TD79F, the reclose fail time delay

M = TD79M, the maximum reclose operation time

Delay = the time delay in cycles, milliseconds, or seconds
A setting of zero disables a timer. An access area 1 or 2 password is required to change

settings.




TD79R 79F 79M

120m 0m 0m

TD791 792 793

50m 1.0s 5.0s