9272000990 Rev J

BE1-BPR Functional Description

4-27

I Command
Purpose:

Reads the primary current value of all or individual phases.

Syntax:

I[<phase>]

Comments:

No access area password is required for reporting functions. Primary and secondary

current values are available through HMI menu branch 2.


I Command Examples:
1. Read Phase B current.

IB

3.23KA
2. Read all primary currents.

I

IA=3.23KA; IB=3.23KA; IC=3.23KA; IN=0.00KA

The DIAG command reads or resets any diagnostic alarms recorded by the relay.

DIAG

Diagnostic alarms

HMI Menu Branch: 2

Parameter

Description

Non-Maskable

Alarms

RAM ERROR: Static RAM read/write error
ROM ERROR: EPROM program memory checksum error
uP ERROR: Microprocessor self test error
EEPROM ERROR: EEPROM read/write error
EEDATA ERROR: EEPROM data checksum error
ADC ERROR: Analog to digital converter error
CALIBRATION ERROR: Relay not calibrated or calibration checksum error
POWER SUPPLY ERROR: Power supply out of tolerance

Maskable

Alarms

ALARM LOGIC (OA): Alarm logic (OA equation) was true
TIMER ALARM (TL): Timer alarm setting exceeded (refer to PTLOG

Command)
CONTACT DUTY ALM (DL): Contact duty maximum (DMAX) exceeded

(refer to BKRCON Command)
BKROP >1 SEC (BKR): Breaker operation (clearing) time was greater than 1

second
POWER RESET (RST): Power supply to microprocessor has been reset
CLOCK NOT SET (CLK): Real time clock not set
RECLOSE FAIL (RF): Reclose attempt failed


DIAG Command
Purpose:

Reads or resets diagnostic information.

Syntax:

DIAG[=0]

Comments:

No access area password is required to read or reset diagnostic information. Entering

DIAG=0 will reset all diagnostics that can be reset.


DIAG Command Example:
View any diagnostic alarms.

DIAG

TIMER ALARM