9272000990 Rev J

BE1-BPR Functional Description

4-43

POSC Command
Purpose:

Reads or programs the number of oscillographic fault records saved.

Syntax:

POSC[=x]

Comments:

x=6, 8, 10, or 12 (default)

Area one, two, or three password access is required to change the maximum number of

oscillographic records.

POSC

Maximum number of oscillographic records

HMI Menu Branch: N/A

Parameter

Setting Range

Pre-Fault Cycles

Post-Fault

Cycles

Cycles Per

Record

x

6

4

36

40

8

4

26

30

10

4

20

24

12

4

16

20

POSC Command Examples:
1. Read the maximum number of fault records that the relay is able to record.

POSC

6
2. Configure the relay to record 30 cycles of oscillography data in each fault record.

POSC=8

Maintenance
Maintenance involves configuring and verifying essential features of the relay. These features may be

programmed through the front panel controls or through the communications ports. The following list of

these features includes the corresponding commands in parenthesis. LCD contrast cannot be adjusted

through the communications ports. Output contact testing cannot be performed through the HMI.

Time and date settings (TIME, DATE, PCLK)

Communication port settings (COM)

Password settings (PW)

Fault detector calibration settings (CAL, FREQ)

HMI liquid crystal display (LCD) contrast

Default HMI display screen (PDISPLAY)

Output contact testing (OUT)

Software version reporting (VER)

Examples of typical MAINTENANCE menu screens are shown below.

MAINTENANCE

menu screen

CAUTION

Changing the POSC command setting will delete all existing fault records stored

in RAM. Fault records can be downloaded and saved prior to making a POSC

command setting change. Section 4, Functional Description, Software Functional

Description, Oscillographic Data Acquisition provides information about using the

FLT command to download and save fault records.