BE1-BPR Communications

9272000990 Rev J

COMMAND FORMAT

Each command consists of an ASCII string terminated by a carriage return, <CR>. A line feed <LF> is

optional. A semicolon may be used to separate multiple commands on a single line, however, the total

line length cannot exceed the size of the communication buffer (40 characters).
Command Format: [<ID>]<CMD1>[<;>CMD2<;>…<;>CMDn]<CR>[<LF>]

where

[ ] = Brackets identify optional parameters - brackets themselves are not part of command.

< > = Separator used for clarity - not an actual part of the command.

ID = Relay identifier used for RS-485 multi-drop (polled) communications.

CMDn = <Name>[#][<=><Setting-1>…[<,><Setting-n>]]

Name = Command name (1 to 8 characters)

# = Numeric or phase identifier to limit command to a specific item.

= = Used to indicate that the command is to change data/settings not to recall data.

Setting-n = Command setting(s).

, = Comma used as setting separator.

; = Semicolon used to separate multiple commands on the same line.

CR = Carriage return used to end command and start execution.

LF = Line feed may be used for clarity. Ignored by relay.

Spaces = One or more spaces may be added between entries for clarity if desired.


Commands received by the BE1-BPR relay consist of two general types: requests for information and

changes to operating parameters. Requests for information will always be accepted and executed,

however changes to operating parameters may be limited to access from personnel with the proper

password. Commands to change parameters are identified by an equals sign, '=', being included in the

command. The new operating parameters to the right of the equals sign are intended to replace the

current operating parameters related to the command.
Some commands may pertain to multiple items. In that case, a numeric or phase identifier is used after

the command name to specify a single item. If the identifier is left off, the command applies to all possible

items. For example, the IA command could be used to read the current on phase A or the I command

without the phase identifier would read the current on all inputs.

Multi-Drop (Polled) Command Operation

Each relay can have a unique identification number programmed from 1-254. If the Relay internal ID is set

to 0 (zero), then polled operation is disabled and the ID prefix is not required as part of the command. If a

non-zero ID is programmed for the relay, the relay ID number must preface each command sent to the

relay through either of the rear communications ports. The command ID is never required from the front

panel communications port.
In polled mode, the relay waits until it is polled (i.e. - receives a command identified for it), then it

responds. Any data string that does not start with the proper ID will be ignored.
A unique ID is reserved to communicate with ALL relays operating in multi-drop mode and connected to

the same network. Any command prefaced by an ID of '!' will cause all Relays receiving the command to

execute the command but not to respond (BROADCAST OPERATION - NO RESPONSE). This type of

operation allows commands to be executed simultaneously by multiple relays. For example, 17TIME

would read the current time setting of Relay 17 and !TIME=12:05:37 would simultaneously set all relays

on network to the new time entered.

NOTE

For polled operation over the RS-485 interface, the hardware handshake

(RTS/CTS), software handshake (XON/XOFF), and echo options must be

disabled on COM1 (i.e. COM1=,H0,E0,X0).