Lcd contrast adjustment, Default hmi display screen, Output contact testing – Basler Electric BE1-BPR User Manual

Page 102

Advertising
background image

4-50

BE1-BPR Functional Description

9272000990 Rev J

The LCD contrast may be adjusted from the front panel using the LCD CONTRAST menu screen.

Pressing the EDIT +/- key will scroll through an adjustment range of 1 to 20 with 10 being the nominal

setting.

LCD Contrast Adjustment

The default HMI screen is displayed when there are no targets and no HMI key has been pressed for

more than four minutes. Unless programmed differently, the default HMI screen is the TARGETS screen.

Using the PDISPLAY command, any display screen can be set as the default screen. Refer to Figure 4-2

(enhanced relays) or Figure 4-3 (standard relays) for menu display maps.

Default HMI Display Screen

PDISPLAY

Default HMI display screen

HMI Menu Branch: N/A

Parameter

Parameter Selections

Comments

default_menu Menu branch 0, 1, 2, 3, 4, 5, or 6 for

Enhanced relays.
Menu branch 0, 1, 2, 3, 4, or 5 for

Standard relays.

The default screen is programmed

by entering the number of screens

to the right of the target screen

(default_menu) and down from the

top of screen of the menu branch

(default_screen).

default_screen number of screens down from the top

screen (0) of the menu branch


PDISPLAY Command
Purpose:

Read or program the default HMI display screen.

Syntax:

PDISPLAY[=<default_menu>,<default_screen>]

Comments:

Access area password one, two, or three required to change settings. Default setting is

0,0.


PDISPLAY Command Examples:
1. Set the primary current display screen (menu branch 2, screen 2) as the default display.

PDISPLAY=2,2

2. Set the target display screen (menu branch 0, screen 0) as the default display.

PDISPLAY=0,0

The OUT command provides the means to test the relay outputs by pulsing the outputs either on or off.

Outputs are pulsed on or off for 200 to 250 milliseconds and can be tested individually or collectively.

Output Contact Testing

OUT

Output testing

HMI Menu Branch: N/A

Parameter

Parameter Selections

Comments

1/0

1 (on)
0 (off)
enable (enables test)
disable (disables test)

1 pulses OUTx for 200 to 250 ms
0 pulses OUTx off for 200 to 250 ms
OUT=ENABLE enables OUT testing
OUT=DISABLE disables OUT testing
Default setting is OUT=DISABLE


NOTE

Assigning any continuously updated HMI screen (2,1 / 2,2 / 2,3 / 6,1) as the

default display will result in slower serial port communication.