Basler Electric BE1-BPR User Manual

Page 132

Advertising
background image

6-4

BE1-BPR Communications

9272000990 Rev J

The following procedure describes how relay settings can be read, modified, saved to a file, and uploaded

to BE1-BPR relays. Any commercially available communications software may be used. Instructions for

configuring Windows HyperTerminal® are provided in Appendix A, Terminal Emulation.
1. Obtain password access to area one and use the SHOWSET command to obtain a report of all relay

settings. Getting password access to area one before using the SHOWSET command will ensure that

all passwords are displayed in the settings report. If password access is not obtained, passwords will

be displayed as asterisks (********).

2. Once the settings are displayed, copy the settings to a text editor such as Microsoft

Notepad

.

3. Edit the settings by making changes and deletions where required. You should ensure that each

command is terminated with a carriage return or semicolon and that line length does not exceed 40

characters. An example of settings that were read using the SHOWSET command and then copied to

a text editor is shown below. Text and settings that must be removed prior to uploading are shown

shaded in gray. The

PRESS ANY KEY TO CONTINUE… message can be avoided by setting the page

mode at P0 in the BE1-BPR communication settings. This setting is recommended if your terminal

emulation software included a scroll buffer.

PW1=AREA1PW,B; PW2=AREA2PW,B; PW3=AREA3PW,B; PW4=AREA4PW,B

LN=USER

LF1=PI,1; LF2=NI,1; LF3=PI,2

LI1=4,12; LI2=4,12; LI3=4,12; LI4=4,12; LI5=4,12

LI6=4,12; LI7=4,12

LR=0,0,0,0,0

LT1=D,O8,/O8; LT2=D,O9,/O9; LT3=C,O10,/O10; LT4=D,O6,/O6; LT5=D,O12,/O12

LT6=0,0,0

LOA=T4+O15

LO1=O3

LO2=O3

LO3=T1O7+F1T2+O1O7

LO4=T5

LO5=T3

LO6=/I1/I2

LO7=F1+F2

LO8=T3O11

LO9=T3I6+T3I7

LO10=I6+I7+O11

LO11=I3+I4+I5

LO12=F3I1

LOGIC=USER

FREQ=60

ID=0

PU1=1.00; PU2=1.00; PU3=1.00,10

TD1= 20m; TD2= 20m; TD3= 20m; TD4= 20m; TD5= 20m

TD6= 20m

TD791= 111m; TD792= 111m; TD793= 111m; TD79R= 111m; TD79F= 111m

TD79M= 111m

CTP=1; CTN=1

PHOLD=11111

SNAME=5,SUBSTATION_1

PCLK=M,24

PDISPLAY=0,0

COM0=96008N1,A0,E0,H0,P0,X0

COM1=96008N1,A0,E0,H0,P0,X0

PTARGET=0011111,11110

TRIGGER=O5

PTLOG1=0,L,0m; PTLOG2=0,H,11m; PTLOG3=0,L,11m; PTLOG4=0,H,12m; PTLOG5=0,L,13m

PTLOG6=0,H,14m

PDIAG=00000000,00000000

BKRCON=0.000E+00,0,0

BKROPS=,I1

BKRRES=0,0,0.000E+00

Advertising