BE1-BPR Installation

9272000990 Rev J

Figure 7-16. RS-422/RS-485 DB-37 to BE1-BPR Cable Connection

IRIG Input and Connections
The IRIG input is fully isolated and accepts a demodulated (dc level-shifted) signal. The input signal must

be 4.5 volts or higher to be recognized as a high logic level. Maximum input signal level is 25 volts. Input

burden is nonlinear and rated at 4 kΩ at 5 Vdc.
IRIG connections are located on a terminal clock shared with the RS-485 terminals. Terminal

designations and functions are shown in Table 7-4.

Table 7-4. IRIG Pinouts

Terminal

Function

Reference

+

Signal