Basler Electric BE1-BPR User Manual
Page 135
9272000990 Rev J
BE1-BPR Communications
6-7
ID Command
Purpose:
Reads or programs a relay ID number for polled communication.
Syntax:
ID [=<id(0-255)>]
Reference:
Section 4, Functional Description, Software Functional Description, Maintenance,
Communication Settings
LF Command
Purpose:
Reads or changes the fault detector logic of the active logic scheme.
Syntax:
LF[x][=<type>,<filter>]
Reference:
Section 4, Functional Description, Software Functional Description, Relay Setup, Fault
Detectors
LI Command
Purpose:
Reads or programs contact input logic.
Syntax:
LI [#[=<r>,<db>]]
Reference:
Section 5, BESTLOGIC Programmable Logic, Contact Input Logic, Definition of Input
Contact Operation
LINFO Command
Purpose:
Reads the names of all logic schemes in memory or the equations associated with the
named logic scheme.
Syntax:
LINFO[<name>]
Reference:
Section 5, BESTLOGIC Programmable Logic, General
LN Command
Purpose:
Reads the name of the active logic or program a new set of logic equations called
<name>.
Syntax:
LN[=<name>]
Reference:
Section 5, BESTLOGIC Programmable Logic, Logic Names
LO Command
Purpose:
Reads or programs output logic.
Syntax:
LO [#[=<Boolean equation>]]
Reference:
Section 5, BESTLOGIC Programmable Logic, Programming Output Operational
Characteristics
LOGIC Command
Purpose:
Reads or changes the active logic of the relay.
Syntax:
LOGIC[=<existing name>]
Reference:
Section 5, BESTLOGIC Programmable Logic, General
LR Command
Purpose:
Reads or programs the recloser input logic.
Syntax:
LR [=<type>,<start>,<reset>,<wait>,<lockout>]
Reference:
Section 5, BESTLOGIC, Recloser Logic, Programming Definition Characteristics
LT Command
Purpose:
Reads or changes timer logic.
Syntax:
LT[x][=<type>,<start>,<reset>]
Reference:
Section 4, Functional Description, Relay Setup, Timers