BE1-BPR Communications

6-7

ID Command

Purpose:

Reads or programs a relay ID number for polled communication.

Syntax:

ID [=<id(0-255)>]

Reference:

Section 4, Functional Description, Software Functional Description, Maintenance,

Communication Settings


LF Command

Purpose:

Reads or changes the fault detector logic of the active logic scheme.

Syntax:

LF[x][=<type>,<filter>]

Reference:

Section 4, Functional Description, Software Functional Description, Relay Setup, Fault

Detectors


LI Command

Purpose:

Reads or programs contact input logic.

Syntax:

LI [#[=<r>,<db>]]

Reference:

Section 5, BESTLOGIC Programmable Logic, Contact Input Logic, Definition of Input

Contact Operation


LINFO Command

Purpose:

Reads the names of all logic schemes in memory or the equations associated with the

named logic scheme.

Syntax:

LINFO[<name>]

Reference:

Section 5, BESTLOGIC Programmable Logic, General


LN Command

Purpose:

Reads the name of the active logic or program a new set of logic equations called

<name>.

Syntax:

LN[=<name>]

Reference:

Section 5, BESTLOGIC Programmable Logic, Logic Names


LO Command

Purpose:

Reads or programs output logic.

Syntax:

LO [#[=<Boolean equation>]]

Reference:

Section 5, BESTLOGIC Programmable Logic, Programming Output Operational

Characteristics


LOGIC Command

Purpose:

Reads or changes the active logic of the relay.

Syntax:

LOGIC[=<existing name>]

Reference:

Section 5, BESTLOGIC Programmable Logic, General


LR Command

Purpose:

Reads or programs the recloser input logic.

Syntax:

LR [=<type>,<start>,<reset>,<wait>,<lockout>]

Reference:

Section 5, BESTLOGIC, Recloser Logic, Programming Definition Characteristics


LT Command

Purpose:

Reads or changes timer logic.

Syntax:

LT[x][=<type>,<start>,<reset>]

Reference:

Section 4, Functional Description, Relay Setup, Timers