4-28

BE1-BPR Functional Description

9272000990 Rev J

The PDIAG command is used to configure the diagnostic alarms.

PDIAG Command
Purpose:

Reads or programs service diagnostic alarms.

Syntax:

PDIAG[=<DIAG1 mask>,<DIAG2 mask>]

Comments:

Access area level password 1, 2, or 3 is required to change settings. A diagnostic flag is

enabled by a 1 and disabled by a 0. DIAG1 drives virtual output 14 (O14) AND DIAG2

drives virtual output 15 (O15). Entering PDIAG returns the diagnostic mask for O14 and

O15.

PDIAG

Programmable diagnostic alarms

HMI Menu Branch: N/A

Parameter

Range

Parameter Selections

DIAG1

mask

0 or 1

<(

OA)(TL)(DL)(BKR)(RST)(CLK)(RF)(LO)>

where:
OA - Flag is set when LOA logic becomes true. Flag is reset

when the diagnostic alarms are cleared and the DIAG=0

command is sent. Allows a logic expression written to LOA to be

latched and reported.
TL - Flag is set when any TLOG alarms occur. Flag is reset

using the DIAG=0 command.
DL - Flag is set when any DLOG is ≥ 100% of DMAX. Flag is

reset when the DLOG value is reset.
BKR - Flag is set when the breaker takes more than 1 second

to interrupt the phase current after the breaker is opened. Flag

is reset when the DIAG=0 command is used.
RST - Flag is set when the microprocessor is reset due to a loss

of power or watchdog timer operation. Flag is reset when the

DIAG=0 command is used.
CLK - Flag is set when the time and date have not been set.

Flag is reset when either the time or date is set.
RF - Flag is set when the Reclose Fail Alarm occurs. Flag is

reset when the breaker closes.
LO - Flag is set when the recloser goes to lockout. Flag is reset

when the recloser comes out of lockout.

DIAG2

mask

0 or 1


PDIAG Command Example:
Program virtual output 14 to go high if the recloser lockout (LO) flag is set. Program virtual output 15 to go

high if the alarm logic (OA), timer log (TLOG), duty log (DL), or reclose fail (RF) flags are set.

PDIAG=00000001,11100010

The TEST command provides the same diagnostic information as the DIAG command plus the software

checksum and relay on-line/off-line status.

TEST

Diagnostic data

HMI Menu Branch: N/A

Comments
This command retrieves diagnostic data from the relay. This data includes diagnostic alarms,

the software checksum, and whether the relay is on or off line. The diagnostic alarm

information retrieved by the TEST command is the same information displayed by the DIAG

command. The TEST command is read only; diagnostic alarms should be reset using the DIAG

command.