Breaker resistor protection, Breaker resistor protection -10, Figure 2-12. breaker arc detector circuits – Basler Electric BE1-BPR User Manual

Page 34: Figure 2-13. breaker resistor protection circuits

Advertising
background image

2-10

BE1-BPR Application

9272000990 Rev J

Figure 2-12. Breaker Arc Detector Circuits


The breaker arc detector logic employed in the preprogrammed schemes logically ANDs the MAF fault

detector (F3) and the 52b input (I1) to start a delay timer (T5). Timer delay can be as long as 60 seconds.

The timer delay should be set to 1.5 to 2.0 times the MAF window time. Both the fault detector and

breaker status must stay unchanged for the entire length of the time delay or the timer is reset. If the timer

does time out, the breaker arc output (O4) closes. This output could be used to reclose the breaker,

extinguish the arc, prevent secondary circuit switcher failure, externally parallel the BFO, or to give an

alarm.

Breaker Resistor Protection
Breaker resistor protection is a BE1-BPR relay feature that monitors the number of times a breaker

opening resistor has been used and the amount of elapsed time between operations. If additional

openings (operations) would exceed the resistor maximum power rating, the breaker resistor protection

feature operates output 13 (O13), which can be used as a block reclose output. Breaker resistors are

typically rated to handle X operations (i.e. - 5 operations) in T time (i.e. - 15 minutes cooling time for each

operation). The resistor protection is a self contained module (Figure 2-13) that counts and time tags each

operation then decrements the count T time after it occurred. If the count reaches the limit, an internal

output becomes TRUE. In the enhanced logic schemes, the programmable logic output (O13) drives the

block reclose output. (If a reclosing function is enabled, programmable logic output (O13) is driven by the

reclose output, and the block reclose signal is internally ORed with the defined reclose WAIT logic input.)

This output is intended to block reclosing until the count has dropped below the limit. This action allows

the resistors to cool sufficiently and protects the opening resistors.
Refer to Output Contacts in this section for additional information if your requirements call for a NC

contact for this purpose. Also see Section 4, Functional Description, for a detailed functional description

on how to program the resistor protection function module.

Figure 2-13. Breaker Resistor Protection Circuits

Advertising