Run time group 9 [r.Ixx]
TRACKING VALUES.

NOTES:
1) this run time group will be shown when the instrument

operates in programmer mode only.

2) The tracking function works even if no control output is

configured.

- Tracking group 1 - tracking above - [r.I01]

Lower display: t.A x

where x is the number of the tracking

group (from 1 to 10).

Range: from 1 to 500 digits.
NOTES:
1) The tracking above values will be added to the operative set

point value in order to obtain the high limit used for tracking
and guaranteed soak functions.

2) When a program is running and the tracking above value of

the segment in progress has been modified, the new value
will be immediately used.

- Tracking group 1 - tracking below - [r.I02]

Lower display: t.b x

where x is the number of the traking

group (from 1 to 10).

Range: from 1 to 500 digits.
NOTES:
1) The tracking below values will be subtracted to the operative

set point value in order to obtain the high limit used for
tracking and guaranteed soak functions.

2) When a program is running and the tracking below value of

the segment in progress has been modified, the new value
will be immediately used.

NOTE: For tracking group 2 to 10, the instrument will show on
the lower display the respective tracking group number and it is
possible to perform the same setting described for tracking
group 1.