Super Systems 20PQ User Manual

Page 92

Advertising
background image

88

Gr. 6

Example for A1.Cn (A2.Cn, A3.Cn) = H.L.

A= alarm condition detection
B= the alarm remains in alarm status (even if the measured

value is under the threshold) until a manual reset is
performed (C).

E= if a manual reset is performed when the alarm condition still

exist; the LED gets steady lit, the alarm remains in the alarm
status until the process variable reaches the alarm threshold
minus hysteresis (D).

NOTE:
The manual reset (acknowledgement) may be performed by the
"ñ.rSt" [R.C01] parameter or by logic input or by serial link.

- Alarm 1 action - [r.F03]

This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: dir

= direct action (Relay energized or SSr=1 in

alarm condition)

rEV

= Reverse action (Relay energized or SSr=1 in

non alarm condition)

- Alarm 1 stand by (mask) function - [r.F04]

This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: OFF = Stand-by function disabled

On

= Stand-by function enabled

A

C

A

E

D

OFF

ON

Relay out

Alarm
Hysteresis

Alarm
Threshold

Measured
Value

OFF

ON

LED 1(2, 3)

B

Flash

Flash

Steady

XKP-1-C2.p65

10/30/01, 9:37 AM

88