Super Systems 20PQ User Manual

Page 59

Advertising
background image

55

CnF. 5

NOTE: See also all NOTES of the "d1.Fn" ("Logic input 1
function" [C.H01]) parameter.

- Logic input DIG 2 - contact status - [C.H04]

This parameter will be available only when "d2.Fn" [C.H03] is
different from “nonE”.
Range: CLSd = The input is at logic level “1” when contact is

closed.
When "d2.Fn" [C.H03] is equal to “ru.St”, the
instrument toggles from one status to the other
one when the transition from contact open to
contact close is detected.

OPEn = The input is at logic level “1” when contact is

open.
When "d2.Fn" [C.H03] is equal to “ru.St”, the
instrument toggles from one status to the other
one when the transition from contact close to
contact open is detected.

- Logic input DIG 3 function - [C.H05]

This parameter will be available only when input contact option
is fitted.
Range: nonE = Input contact not used

ru.SL = Input contact used for RUN /HOLD selection.

The status is related to the input level (RUN
when the logic level is "1").
NOTE: when an input is programmed as RUN/
HOLD selector related with the status, the RUN/
HOLD selection by keyboard has no effect.

ru.St

= Input contact used for RUN /HOLD selection.

The instrument toggles from one status to the
other one when the transition selected by
"d3.St" [C.H06] is detected.
NOTE: for more details about the RUN/HOLD
selection, see the related note at pag.54.

Pr.Ab = Input contact used for program abort (Abort

when the logic level is equal to "1").
NOTE: for ABORT function only, the input
status must be maintained for more than 3
seconds.

Pr.SL = Input contact used for program selection (for

more details see NOTE 2) of the "d1.Fn"
("Logic input 1 function" [C.H01]) parameter).