Super Systems 20PQ User Manual

Page 17

Advertising
background image

13

Switching mode: isolated zero crossing type.
Rated current: from 50 mA to 1 A.
Rated voltage: from 24 V

RMS

to 240 V

RMS

-10 % +15 % (50/

60Hz)
Load type: resistive load only
NOTES 1) To avoid electrical shock, connect power line at

the end of the wiring procedure.

2) For power connections use No 16 AWG or larger

wires rated for at last 75 °C.

3) Use copper conductors only.
4) Don’t run input wires together with power cables.
5) This output is not fuse protected. Please, provide it

externally using a fuse with a I

2

t equal to128.

23

Load

24

Line

26

Load

27

Line

OUT 1

OUT 2

NOTE: This output is not isolated.
A double or reinforced insulation between instrument output and
power supply must be assured by the external solid state relay.

E.3) TRIAC OUTPUTS

Fig. 14 TRIAC OUTPUT WIRING

XKP-1-C2.p65

10/30/01, 9:36 AM

13

Advertising