80

Gr. 4

- Hysteresis (for ON/OFF control) of the first
PID group - [r.d10]

This parameter is available when Pb [r.d01]=0 (On/OFF control
action) and the instrument is in programmer mode.
Lower display: HYS x where x is the number of the selected PID

group.

Range: from 0.1% to 10.0% of the input span.

- Integral time of the first PID group - [r.d11]

This parameter is available when at least one control output is
configured, Pb [r.d01] is different from 0 and the instrument is in
programmer mode..
Lower display: ti x

where x is the number of the selected PID
group.

Range: from 00.01 to 20.00 mm.ss

Above this value the display blanks and the integral
action is excluded

NOTE: When device is working with SMART algorithm the “ti”
value will be limited as selected by “ti.Hi” [r.M04] and “ti.Lo”
[r.M03].

- Derivative time of the first PID group - [r.d12]

This parameter is available when at least one control output is
configured, “Cn.tP” [C.G02] is equal to “Pid”, "Pb" [r.d01] is
different from 0 and the instrument is in programmer mode.
Lower display: td x

where x is the number of the selected PID
group.

Range: From 00.00 to 10.00 mm.ss
NOTES:
1) When device is working with SMART algorithm and “Cn.tP”

[C.G02] is equal to “Pid”, the “td” value will be equal to a
quarter of “ti” value.

2) When “Cn.tP” [C.G02] is equal to “Pi”, the derivative action is

excluded