118

Gr. P

- Break event reset at the end of program 1
- [r.A13]

This parameter can be modified only when the selected program
is not running, it is not a linked program and at least one break
event is programmed for the program 1.
Upper display: Pr.xx

where xx is the number of the selected
program.

Range: YES the break events maintain their status after the end

of the program.
NOTE: if a program is aborted, all the break
events maintain the status programmed for the
last executed segment.

nO

all the break events will be reset at the end of
program execution.

- Control type at the end of program 1 - [r.A14]

This parameter can be modified only when the selected program
is not running and it is not a linked program.
Upper display: Pr.xx

where xx is the number of the selected
program

Range: ñout At the end of the program the instrument goes in

manual mode with a power output equal to the
value programmed with the "control output at the
end of the program 1" parameter [r.A15].

ñSP At the end of the program the instrument will

continue to control with a set point value equal to
the value programmed with the "Set point at the
end of the program 1" parameter [r.A16].

OPO At the end of the program the instrument goes in

"Output Power OFF" mode

NOTES:
1) If no control output is configured, this parameter will be forced

to "ñSP".

2) If, due to a modification of the instrument configuration, the

manual function (previously enabled) is disabled and this
parameter is set as "ñout", the "Err" indication will be
displayed and the program execution will be inhibited.

In order to remove the "Err" indication correct the instrument

configuration.

- Control output at the end of program 1
- [r.A15]

This parameter can be modified only when the selected program
is not running, it is not a linked program and "Control type at the
end of the program 1" [r.A14] is equal to ñout.
Upper display: Pr.xx

where xx is the number of the selected
program

Range: from 0.0 to 100.0 % if device is configured with one

control output only.