Super Systems 20PQ User Manual

Page 95

Advertising
background image

91

Gr. 6

- Alarm 3 configuration - [r.F10]

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: H.A.

= High alarm (outside band) with automatic reset

L.A.

= Low alarm (inside band) with automatic reset

H.A.Ac= High alarm (outside band) with automatic reset

and acknowledge

L.A.Ac= Low alarm (inside band) with automatic reset

and acknowledge

H.L.

= High alarm (outside band) with manual reset

L.L.

= Low alarm (inside band) with manual reset

NOTE: When alarm configuration has been changed, the alarm
status will be deleted.

- Alarm 3 action - [r.F11]

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: dir

= direct action (Relay energized or SSr=1 in

alarm condition)

rEV

= Reverse action (Relay energized or SSr=1 in

non alarm condition)

- Alarm 3 standby (mask) function - [r.F12]

This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: OFF = Stand-by function disabled

On

= Stand-by function enabled

NOTES:
1) If the alarm is programmed as band or deviation alarm, this

function masks the alarm condition after a set point change or
at the instrument start-up until process variable reaches the
alarm threshold plus or minus hysteresis. If the alarm is
programmed as a process alarm or control output alarm, this
function masks the alarm condition at instrument start-up until
process variable reaches the alarm threshold plus or minus
hysteresis.

2) The change from On to OFF has immediate effect, while the

change from OFF to On has effect at the next start up or set
point change

XKP-1-C2.p65

10/30/01, 9:37 AM

91

Advertising