37

CnF. 2

- Valve position indication - [C.E06]

This parameter will be displayed only when open loop
servomotor control drive output is configured.
Range: Fb

= The valve position is measured and displayed

no.Fb = The valve position is not measured

NOTE: If the feedback option is not mounted, this parameter will
be forced to “no.Fb” (no feedback).

- OUT 5 function - [C.E07]

Range: nonE = Output not used

ñAin

= Main control output (linear)

SECn = Secondary control output (linear)
PV.rt = Process variable retransmission
SP.rt = Operative set point retransmission

NOTE: When the option circuitry is not mounted the middle
display will show “no.Pr” (not present).

- OUT 5 range - [C.E08]

This parameter will be available only when Out 5 is configured
("O5.Fn" [C.E07] different from "nonE")
Range: 0-20

= 0

¸20 mA

4-20

= 4

¸20 mA

- OUT 5 retransmission initial scale value
- [C.E09]

This parameter will be available only when Out 5 function
[C.E07] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTES:
1) Decimal point is positioned as previously selected at “CnF.1 -

ñ.In.d” [C.d03])

2) The OUT 5 retransmission initial scale value can be higher

than OUT 5 retransmission full scale value [C.E.10].