64

CnF. 6

- Automatic start enabling - [C.I14]

This parameter will be available only when the clock calendar
hardware is mounted.
Range: nonE = The "Automatic start" function is disabled

Cnd.A = the program will start at the programmed time

only if the following conditions are satisfied:
- no other program is running
- no power down is present when the current

time coincides with the programmed start
time;

- when a logic input is programmed for RUN/

HOLD function related input level, the input
level must be "1";

- the instrument isn’t in manual mode.

Cnd.b = at the programmed start time the instrument

verify the above described conditions and, if
one or more conditions are not satisfied, the
instrument will continue to verify it for the
programmed hysteresis time.
If the wrong condition disappeares during the
hysteresis time, the instrument will start the
selected program otherwise it does not start
any program.

- Hysteresis of the Automatic starting - [C.I15]

This parameter will be available only when the clock calendar
hardware is mounted and the "En.Ck" [C.I.14] parameter is set
to "Cnd.b".
Range: from 0.01 (hh.mm) to 6.00 (hh.mm).

- Current time - [C.I16]

This parameter will be available only when the clock calendar
hardware is mounted and the "En.Ck" [C.I.14] parameter is
different from "nonE".
Range: from 0.00 (hh.mm) to 23.59 (hh.mm).

XKP-1-C2.p65

10/30/01, 9:37 AM

64