- Main control output max rate of rise - [r.E06]

This parameter is available when one control output is
configured as main output.
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES:
1) This parameter will be active even if device is configured for

On/OFF control.

2) During the transfert from AUTO to MANUAL, if this action is

programmed as a not bumpless transfer, the “ñ.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.

- Main output cycle time - [r.E07]

This parameter is available when a time proportional main
control output is configured.
Range: from 1 to 200 s

- Secondary control output low limit - [r.E08]

This parameter is available when one control output is
configured as secondary control output.
Range: From 0.0 % of the output span to S.OLH [r.E09].

- Secondary control output high limit - [r.E09]

This parameter is available when one control output is
configured as secondary control output.
Range: from S.OLL [r.E08] to 100.0 % of the output span

- Secondary control output max rate of rise
- [r.E10]

This parameter is available when one control output is
configured as secondary control output.
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES:
1) This parameter will be active even if device is configured for

ON/OFF control.

2) During the transfer from AUTO to MANUAL, if this action is

programmed as a not bumpless transfer, the “S.rñP” function