Super Systems 20PQ User Manual

Page 126

Advertising
background image

122

NOTES:
1) When the final set point of a ramp has been modified and the

next segment is a soak, the instrument automatically modifies
the final set point of the next segment also.
In this way, the next segment remain a soak with a set point
equal to the new value.
If the two segments following the ramp are soaks, only the
first segment remains a soak, the second one become a
ramp with a time duration according to the notes 2, 3 and 4.

2) When, changing a final set point, a soak becomes a ramp or

viceversa and the two eng. units are hh.mm and mm.ss or
viceversa, the instrument will use the old programmed value
with the new time base (for example 10 hours and 30 minutes
becomes 10 minutes and 30 second or 45 minutes and 00
second become 45 hours and 0 minutes).

3) When, changing a final set point, a soak becomes a ramp and

the ramp eng. units is a gradient, the instrument will multiply
the two MSD of the old programmed value (the hours or the
minutes according to the selected "Soak time engineering
unit") to 60 and than add to the moltiplication result the two
LSD (the minutes or the seconds according to the selected
"Soak time engineering unit"); the resulting value is used as
gradient.

4) When the final set point of a ramp has been modified and the

ramp becomes a soak and the eng. unit of the ramp was
equal to "GrAd", the instrument sets the soak time of this
segment equal to 1 (1 second or 1 minute according to the
selected "Soak time engineering unit").

HOW TO ADD A SEGMENT IN AN EXISTING SIMPLE
PROGRAM
When it is desired to add a segment to the end of a program, it
is sufficent:
1) select the Group P (EDIT mode);
2) select the desired program;
3) reach the last programmed segment;
4) when the instrument displays the final set point of the next

segment with the "End" indication, modify this value;

5) set the remaining parameters of the new segment;
It is now possible to exit from edit mode.

When it is desired to add a segment between segment x and
segment x+1, proceed as follows:
1) select the Group P (EDIT mode);
2) select the desired program;

XKP-1-C2.p65

10/30/01, 9:37 AM

122

Advertising