CnF. 3

We will set:

Bias 1 = 0
Gain 1 = 100 / (33.3 - 0) = 3
Bias 2 = - 33.3
Gain 2 = 100 / (100 - 33.3) = 1,5

The bias and gain of the two split outputs are the following:
“ñC.bS” [C.F03] is the Bias 1 applied to the main output
“ñC.Gn” [C.F02] is the Gain 1 applied to the main output
“SC.bS” [C.F05] is the Bias 2 applied to the secondary output
“SC.Gn” [C.F04] is the Gain 2 applied to the secondary output

- Main control output gain - [C.F02]

This parameter will be available only when the split range is
enabled ("SPLt." [C.F01] = "Enb").
Range: from 0.50 to 5.00.

- Main control output bias - [C.F03]

This parameter will be available only when the split range is
enabled ("SPLt." [C.F01] = "Enb").
Range: from -100.0 to 100.0 % of the output span.

- Secondary control output gain - [C.F04]

This parameter will be available only when the split range is
enabled ("SPLt." [C.F01] = "Enb").
Range: from 0.50 to 5.00

- Secondary control output bias - [C.F05]

This parameter will be available only when the split range is
enabled ("SPLt." [C.F01] = "Enb").
Range: from -100.0 to 100.0 % of the output span.