Run time group 5 [r.Exx]
AUXILIARY CONTROL PARAMETER

- Anti reset wind up - [r.E01]

This parameter is available when at least one control output is
configured and "Pb" [r.d01] is different from 0.
Range: from 10% to 200% of the input span

- Servo motor travel time - [r.E02]

This parameter is available when the open loop servomotor
control drive output is configured (“O3.Fn” [C.E03] is equal to
“ñC.Sñ” or “SC.Sñ” and “Sñ.tP” [C.E05] is equal to “OPEn”).
Range: from 0.12 to 3.00 m.ss

- Servo motor dead band - [r.E03]

This parameter is available when the servomotor control drive
output is configured (“O3.Fn” [C.E03] is equal to “ñC.Sñ” or
“SC.Sñ” ).
Range: from 1% to 50%

- Main control output low limit - [r.E04]

This parameter is available when one control output is
configured as main output.
Range: from 0.0 % (of the output span) to ñ.OLH [r.E05]

- Main control output high limit - [r.E05]

This parameter is available when one control output is
configured as main output.
Range: from ñ.OLL [r.E04] to 100.0 % of the output span.