Proportional Band: programmable from 0.5% to 999.0% of the
input span.
Setting a PB equal to 0 the control action becomes ON/OFF.
Hysteresis (for ON/OFF control action): programmable from
0.1% to 10.0 % of the input span.
Integral time: programmable from 1 second to 20 minutes or
excluded.
Derivative time: programmable from 1 second to 10 minutes or
excluded.
Integral pre-load: programmable
- for one control output, from 0 to 100% of the output range.
- for two control outputs (split range excluded), from -100 % to

+100 % of the output range.

Anti reset windup: from 10 % to 200 % of the input span.
Main output cycle time: from 1 second to 200 seconds.
Secondary output cycle time: from 1 second to 200 seconds.
Relative secondary output gain: keyboard programmable from
0.20 to 2.00 referred to the proportional band.
Overlap / dead band : keyboard programmable from - 20 %
(dead band) to + 50 % (overlap) of the proportional band.

CONTROL ACTIONS
Algorithm
: PID + SMART
Types:
- one control output (digital or analog output)
- one control output splitted on two outputs.
- two control outputs
NOTE: the outputs can be freely selected among analog, digital

or servo outputs.

Digital output types:

Relay, SSR or TRIAC.

Digital output action type:

Proportional time

Analog output types: 20 mA.
Servomotor output:

Two relays with interlocked contact

Servomotor output type:
- Close loop
- Open loop with valve position indication
- Open loop.
PID group: this instrument allows to set up to 5 PID group.

It is possible to assign one PID group to each program
segment.