Super Systems 20PQ User Manual

Page 16

Advertising
background image

12

The same problem may occur when a switch is used in series
with the internal contacts as shown in Fig. 12.

Fig. 12 EXTERNAL SWITCH IN SERIES WITH THE INTER-

NAL CONTACT

In this case it is recommended to install an additional RC
network across the external contact as shown in Fig. 12
The value of capacitor (C) and resistor (R) are shown in the
following table.

Anyway the cable involved in relay output wiring must be as far
away as possible from input or communication cables.

E.2) VOLTAGE OUTPUTS FOR SSR DRIVE

Fig. 13 SSR DRIVE OUTPUT WIRING

Logic level 0: Vout < 0.5 V DC.
Logic level 1:
14 V + 20 % @ 20 mA
24 V + 20 % @ 1 mA.
Maximum current = 20 mA.

LOAD

(mA)

<40 mA
<150 mA
<0.5

A

C

(

mF)

0.047

0.1

0.33

R

(

W)

100

22
47

P.

(W)

1/2

2
2

OPERATING

VOLTAGE

260 V AC
260 V AC
260 V AC

R

C

LOAD

LINE

+

_

_

+

24

25

OUT 1

SOLID STATE

RELAY

+

_

_

+

27

28

OUT 2

SOLID STATE

RELAY